- Model NO.: XRNM3A- (3.6~12)/ -50
- Type: Current Fuse
- Shape: Circle
- Fusing Device: Fuse Link
- Transport Package: Carbon
- Origin: Xi′an
- Breaking Capacity: High
- Usage: High Voltage
- Fusing Speed: FF
- Trademark: ZhenLi
- Specification: silver, ceram
- HS Code: 8535100000
Model
International model  XRNM3A- (3.6~12)/ -50
Equivalent model
BS standard:
Basic parameters as per DIN standard
Â
Product Model | Equivalent Model |
Rated Voltage (kV) |
Rated Current of Fuse Element (A) |
 Standard Size | Rated Breaking Current (kA) | |
φA(mm) | L(mm) | |||||
XRNM3A-7.2 |
WDLDJ |
7.2 |
25, 31.5, 40, 50, 63 | φ51 |
292 |
50 |
WELDJ | 63, 80, 100 | φ66 | ||||
WFLDJ | 125, 160 | φ76 | ||||
WXLDJ | 160, 200, 224, 250, 315 | φ88 | ||||
WFMDJ | 25, 31.5, 40, 50, 63, 80, 100, 125, 160 | φ76 | 442 | |||
WKMDJ | 200, 224, 250, 315 | φ76 | ||||
XRNM3A-12 |
WDLDJ |
12 |
20, 25, 31.5, 40, 50 | φ51 |
292 |
50 |
WELDJ | 50, 63, 80 | φ66 | ||||
WFLDJ | 80, 100, 125 | φ76 | ||||
WXLDJ | 160, 200 | φ88 | ||||
WFMDJ | 25, 31.5, 40, 50, 63, 80, 100 | φ76 |
442 |
|||
WKMDJ | 125, 160 | φ76 | ||||
WXMDJ | 200, 224 | φ88 |
Outline dimensions as per DIN standard
Fig. 1 Outline drawing of XRNM3A fuse link
 (1)Bus fuse
Model | Equivalent model | Rated Voltage  (kV) |
Rated Current of Fuse Link  (A) |
Main Dimensions (mm) | Rated Breaking Current  (kA) | |||
A | B | C | D | |||||
XRNM3A-3.6 | WDF.0 | 3.6 | 50, 63, 80, 100, 125 | 377 | 254 | 305 | Φ51 | 50 |
WFF.0 | 125, 160, 200 | Φ76 | ||||||
WKF.0 | 250, 315, 355, 400 | |||||||
XRNM3A-7.2 | WFF.0 | 7.2 | 25, 31.5, 40, 50, 63, 80, 100, 125, 160 | 486 | 403 | 454 | Φ76 | 50 |
WKN.0 |
200, 224, 250, 315, 355 |
|||||||
XRNM3A-12 | WKX.0 | 12 |
25, 31.5, 40, 50, 63, 80, 100, 125, 160, 200, 224 |
683 | 600 | 650 | Φ76 | 50 |
Outline drawing of bus fuse
Basic outline parameters of plug-in fuse
in mm
         Size code Model   |
A | B | C | D | E | F | G |
WDF*0 |
390 |
312 |
80 |
140 |
246 |
254 |
φ51 |
WEF*0 |
φ76 |
||||||
WKF*0 | |||||||
WFN*0 | 500 | 461 | 150 | 160 | 266 | 403 | |
WKN*0 | |||||||
WFX*0 | 690 | 659 | 350 | 160 | 268 | 600 |
Main technical data:
The fuse under specified operating conditions is able to reliably break any fault current from the minimum breaking current (1.6~3) ln to the rated breaking current 50kA.
Time - current characteristic curve is as shown in Fig. 4, Fig. 5 and Fig. 6.
Current limiting characteristic curve is as shown in Fig. 7.
Rational use of fuse
The rated current of the fuse for direct start shall be selected according to the following formula
Iy=NInδ
Where,
In- full load current of motor
δ- Coefficient of colligation as shown in the following table
N-Â Ratio of starting current to full load current, generally N = 6
Iy-Current value during start-up
Starting Frequency n/h | 2 | 4 | 8 | 16 |
δ | 1.7 | 1.9 | 2.1 | 2.3 |
Â